1000EXAJ
Hot water/Steam Gene-Link is a Gene-Link with waste steam regenerator added. This Gene-Link can utilize the wasted steam which has a higher temperature than hot water so the waste heat is converted efficiently into cooling, raising the energy efficiency as a result. Another feature is that, large amount of the waste heat can be recovered by one single chiller unit so engine generators with a larger power-generating capacity can be introduced. The amount of gas consumed is cut by giving priority to the use of waste hot water and waste steam.
Furthermore, at load below 68%, the chiller can be operated by only wasted heat.
  • During partial load operations, priority is given to the use of waste hot water so the volume of steam consumed can be significantly reduced.

Hot water/steam GeneLink absorption chiller 1000EXAJ Specifications:

  • Chilled Water Flow Rate (m3/hr)

    378
  • Cooling Capacity (kW)

    3516
  • Heating capacity (kw)

    2695
  • Fuel or steam reduction rate (DURING RATED HEATING OPERATIONS) %
    40
  • Fuel or steam reduction rate (DURING RATED COOLING OPERATIONS)%
    60
  • Chilled water outlet temperature (℃)
    7
  • Chilled water inlet temperature (℃)
    15
  • Cooling water inlet temperature (℃)
    32
  • Cooling water outlet temperature (℃)
    37
  • Min waste hot water temperature (℃)
    80
  • Max waste hot water temperature (℃)
    90
  • Steam pressure (Mpa)
    0.78
  • cop
    1.5
  • series
    EXAJ
  • cooling water flow rate (m3/hr)
    880
  • Fuel or steam reduction rate (DURING RATED HEATING OPERATIONS) %

    40
  • Fuel or steam reduction rate (DURING RATED COOLING OPERATIONS)%

    60
  • Chilled water outlet temperature (℃)

    7
  • Chilled water inlet temperature (℃)

    15