The ARC6 is a ring-type current transformer.

  • Located around cable for all switchgear units: D01N, D02N, D06N and D06H

  • Offers higher accuracy than ARU1 when primary current is less than 600 A

  • Only installed on single-core screened cable with a deeper cable compartment door in single cable per phase applications

ARC6 Specifications:

  • Max. Available Power (kVA)

    0.015
  • Max. Short-term Current (A)

    25000
  • Time of the short duration of current (s)

    3
  • Max. Primary rated current (A)

    600
  • Min. Primary rated current (A)

    5