Search
Companies

Cast Resin Transformer

Evaluate this Device

EWT Transformer Sdn. Bhd.

The factory price is not specified
LEEP: Not Available
Suggest a Price
Download Catalog

EWT Cast Resin Transformer (CRT) are designed based on latest standards to meet the sub stations requirements in urban areas especially in high rise buildings, public amenities with high population density.

  • Fully type tested with KEMA certificate and passed/comply with all the usual quality standards such as Fire Class (F1), Environmental Class (E2), Climatic Class (C2).

  • Low losses, low partial discharge, low noise and strong capacity of heat resistant, 150% overload with cooling fan.

  • Safe, flameproof and no pollution.

  • Maintenance free, easy installation and low cost.

  • LV & HV winding shall be insulation Class F & maximum temperature rise shall be limited to 100K at 40˚C ambient.

ECRN 630/10 Specifications:

  • Width (m)

    1.4
  • Height (m)

    2.2
  • length (m)

    2.1
  • Weight (kg)

    2345
  • Max. Available Power (kVA)

    630
  • Series

    ECRN
  • No-load losses (W)

    1300
  • With-Load Losses (W)

    5200
  • Max. High Voltage (V)

    11000
  • Max. Low Voltage (V)

    433